Page 132 - GRIHA Manual Volume III - Introduction to National Rating System
P. 132
Annexures 125













AnnexuRe-7






Recommended Lighting Power Density (LPD) as per
Energy Conservation Building Code -2007



Interior Lighting Power—Building Area Method
Building area type LPD (W/m ) Building area type LPD (W/m )
2
2
Automotive facility 9.7 Multi-family residential 7.5
Convention centre 12.9 Museum 11.8
Dining : Bar lounge/Leisure 14.0 Ofice 10.8
Dining : Cafeteria/Fast food 15.1 Parking garage 3.2
Dining family 17.2 Performing arts theatre 17.2
Dormitory/Hostel 10.8 Police/Fire station 10.8
Gymnasium 11.8 Post Ofice/Town hall 11.8
Healthcare clinic 10.8 Religious building 14.0
Hospital/Health care 12.9 Retail/Mall 16.1
Hotel 10.8 School/University 12.9
Library 14.0 Sports arena 11.8
Manufacturing facility 14.0 Transportation 10.8
Motel 10.8 Warehouse 8.6
Motion Picture Theatre 12.9 Workshop 15.1

In cases where both a general building area type and a speciic building area type are listed, the speciic building area type shall
be valid.
Source: Energy Conservation Building Code -2007