Page 67 - GRIHA Manual Volume V - Introduction to National Rating System
P. 67
60 Griha Manual: Volume 5




13.2.7 lighting level simulation result outputs for all areas to demonstrate lighting level
compliance with biS (refer table 13.9)

Table13.9 Format for artiicial lighting level calculation
Space name (should be Room area (m ) Upload required Calculated average Recommended
2
same as in architectural documents * lighting (lux) levels on lighting as per NBC
drawing) work plane (link to select list of
spaces with NBC 2005
recommended lux levels)


13.2.8 Provide certificates from architect/service consultant on compliance with clause 13.1.4.
13.2.9 Provide certificates from architect/service consultant on compliance with clause 13.1.5.


13.3 Appraisal (maximum points 8 and mandatory points 6)

13.3.1 by adopting appropriate climate-responsive building design with the limited wwr
and/or Srr as mentioned above, and ensuring that all the fenestrations meet the ShgC
requirement of eCbC-2007, as per clause 13.2.3 and 13.2.5. (2 points – mandatory)

13.3.2 minimum 25% of the living area (as mentioned above) should be daylighted and
adequate level of daylight is provided as prescribed by iS code as per clause 13.1.2 and
13.1.3 (2 points – mandatory) and/or
• If the total daylighted area > 50% of total living area (1 point – additional) and/ or
• If the total daylighted area > 75% of total living area (1 point – additional)


13.3.3 overdesign of lighting system is avoided as per clause 13.1.5 (2 points – mandatory)



Evaluation procedure


Appraisal 13.3.1

by adopting appropriate climate-responsive building design with the limited wwr and/or Srr as
mentioned above, and ensuring that all the fenestrations meet the ShgC requirement of eCbC-
2007, as per clauses 13.2.1–13.2.5. (2 points – mandatory)

Required documentation

1) Site plan showing north point, all building plans with internal layout showing the functional
spaces and interior layout, four side elevations, building sections and fenestration details.
2) details of sun path analysis for each exposed fenestration or use of shading norms to
demonstrate the use of optimum shading devices.
3) detail window and skylight schedule of the proposed building.
4) Submit the detail calculation in the prescribed format for wwr and/or format for Srr; to
demonstrate the percentage of vertical fenestration on gross wall area and/or percentage
of horizontal fenestration on gross roof area.