Evaluation procedure 109



CRIteRIon 27






MInIMIze ozone

depletInG substAnCes





GRIHA-speciic information

Objective

eliminate or control the release of ozone-depleting substances into the atmosphere. the
ozone depleting materials commonly used in buildings are CfCs or hCfCs in refrigeration and
air-conditioning systems, halons in fire suppression systems and extinguishers, and in insulation.


Table 27.1 Ozone depleting potential (ODP) of some commonly used substances
Substance ODP
R11 1
R12 0.9
R22 0.05
R134a <0.0005
R143a 0
R717 (ammonia) 0
R744(CO 2 ) 0
27. 1 Commitment

27.1.1 use insulation with zero-odP such as hCfC-free rigid insulation foam insulation, mineral
fibre board, cork wool, expanded (bead) polystyrene, recycled newspaper, jute, and
cotton. avoid materials that do not inherently have a zero-odP, such as polyurethane
foams and polyisocyanurates.
27.1.2 install CfC- free equipment for refrigeration and air conditioning
27.1.3 install halon-free fire suppression systems and fire extinguishers in the building
27.2 Compliance

the following documents are to be submitted.
27.2.1 a certificate from the manufacturer and supplier, signed by the architect and the
engineer, stating that 100% of the insulation used in the building is free of CfCs and
hCfCs.
27.2.2 the bill of quantity clearly demonstrating that 100% or total quantity of all the insulation
used in the building is free of CfCs and hCfCs.
27.2.3 a certificate from the hvaC consultant or supplier, signed by the architect or engineer,
stating that the hvaC and refrigeration equipments and systems installed in the
building are free of CfCs.